Description
Technical Specifications
- Supply Voltage: 3-Phase 415V AC, 50 Hz (R, Y, B & N).
- Auxiliary Supply: None required; it draws power directly from the monitored input.
- Output Contacts: Two SPDT (C-NO/O-NC) relay outputs, rated at 5A, 250V AC.
- Mounting: Standard DIN Rail.
- Physical Dimensions: 55(W) x 75(H) x 110(D) mm.
- Default Setpoints: Under-voltage default 360V; Over-voltage default 450V; Unbalance default 70V. [1, 2]
Key Protective Functions
-
- Under/Over Voltage: Trips if voltage falls below or exceeds user-defined limits.
- Single Phasing Preventer (SPP): Instantly disconnects power if any single phase fails.
- Reverse Phasing: Shuts down the system if the phase sequence is incorrect.
- Voltage Unbalance: Detects unbalances between phases that cause motor overheating. [1, 2]
Interface & Indicators-
- Digital Display: Shows current running voltage data and explicit fault text messages.
- LED Status Flags: Dedicated Red LED for faults (UV, OV, SPP) and a Green LED indicating the relay status is active.
- 3-Button Settings: Built-in SET, UP (INC), and DOWN (DEC) keys for easy field calibration. [1, 2, 3]
If you are looking to purchase this or configure a system, let me know: -





Reviews
There are no reviews yet.